DC and AC Voltage Transducers, Conditioner, Isolator modules

DC and AC Voltage Transducers, Conditioner, Isolator modules

The VT7 and VT8 series voltage transducers are designed for measuring AC+DC and AC voltages in single-phase, split-phase, and three-phase systems. These models allow isolation, conditioning, and conversion of AC and DC voltages to a proportional RMS, mean, or instantaneous output.

With true RMS sensing, the VT8 series enables precise measurement of distorted waveforms up to the 9th harmonic with a crest factor of 5. Both the VT7 and VT8 transducers can handle distorted waveforms, making them ideal for environments like VFD controllers, UPS systems, and thyristor drives. Additionally, these voltage transducers offer 2.5kV isolation between the input and output, making them perfect for use in systems such as PLC computer systems, analog meters, and energy management systems.
VT7 and VT8 AC / DC Voltage Transducers

DC to 10kHz Frequency Range
For Isolation and Conditioning of AC/DC Voltages

Key Features:

Wide Frequency Range: From DC to 10kHz.
Input Ranges: Available for 50mV to 1000V.
High Isolation: 2.5kV dielectric isolation between input and output.
Output Configurations:
0-1mA
4-20mA (4mA live zero)
0-5V
0-10V
RMS Calibration (VT8 series): Accurate voltage measurement of AC, AC+DC, or distorted waveforms, with support for up to the 9th harmonic.
Auxiliary Power Supply: Ensures output signal availability even when input is near zero.

Applications:

Measurement of AC and DC voltages in environments with distorted waveforms, including:
Pump speed controllers
Fan speed controllers
Motor VFD controllers
UPS and thyristor drives
Suitable for use in:
Energy management systems
Switchboards
Generator and telemetry controls
Shunt isolation and input isolation for systems requiring voltage measurement.

VT7 & VT8 DC & RMS AC / DC Voltage Transducers:

Model VT7: DC voltage transducer, producing an output proportional to the input from DC to 10kHz.
Model VT8: True RMS voltage transducer, providing a DC output that represents the RMS value of the input across a DC to 10kHz frequency range.

Technical Specifications:

Input Ranges:
50mV to 1000V for AC and DC voltage inputs.
Output Types:
0-1mA
4-20mA
0-5V
0-10V
4-12-20mA (optional rescaling and voltage input available).
Auxiliary Power Options:
95-135Vac, 230Vac, and 12V-48Vdc options are available, ensuring flexibility across a wide range of applications.
Isolation:
2500Vac dielectric test.
2.5kV isolation between input and output, ensuring the safety and integrity of the signal.

Instrument Power Options:

Option “-11”: 95-135Vac, 50/60Hz, 5VA.
Option “-22”: 230Vac, 50/60Hz, 5VA, ±15%.
Options “-12, -15, -24, -37, -48”: 12Vdc through 48Vdc (±10%), max current draw 150mA.

Input and Output Voltage Transducer Models:

Millivolt Inputs:
0-50mV: VT7-015B / VT8-015E / VT7-015D / VT8-015X5
0-100mV: VT7-016B / VT8-016E / VT7-016D / VT8-016X5
0-200mV: VT7-017B / VT8-017E / VT7-017D / VT8-017X5
0-250mV: VT7-018B / VT8-018E / VT7-018D / VT8-018X5

Voltage Inputs:
0-10V: VT7-001B / VT8-001E / VT7-001D / VT8-001X5
0-25V: VT7-002B / VT8-002E / VT7-002D / VT8-002X5
0-50V: VT7-003B / VT8-003E / VT7-003D / VT8-003X5
0-100V: VT7-004B / VT8-004E / VT7-004D / VT8-004X5
0-250V: VT7-006B / VT8-006E / VT7-006D / VT8-006X5
0-500V: VT7-009B / VT8-009E / VT7-009D / VT8-009X5
0-1000V: VT7-014B / VT8-014E / VT7-014D / VT8-014X5

Application Examples:

VT7 Series: Used as a high-voltage isolator or millivolt shunt isolator.
VT8 Series: Ideal for measuring RMS AC and DC voltages in systems with distorted waveforms like motor drives, VFDs, UPS systems, and energy management systems.

The VT7 and VT8 AC/DC voltage transducers ensure accurate, isolated measurement of AC and DC voltages across a wide range of applications, from shunt isolation to distorted waveform measurement in complex industrial systems.

VT7-VT8-1 Datasheet